07.CO N FI G U R A B L E INPUTS AND OUTPUTS 69
• Energize on motor start delay:
Provides a delayed energization of relay when
motor is started.
• De-energize on motor stop delay:
Provides a delayed de-energization of relay when
motor is stopped.
• Fieldbus control:
The relay can be energized or de-energized via the
serial port.
• DI9 /DI 10/DI 11 status (M10x 24VDC type):
The relay energizes on DI9/DI 10/DI11 status "1"
• DI0/DI1/DI2 status(M10x AC type ):
The relay energizes on DI0/DI 1/DI2 status "1"
• Trips:
This is a general trip indication function which
include the trips initiated across different motor
states, i.e. motor running, stopped and at fault.
The relay is activated when a trip occurs while
motor is running. The relay is also activated to the
faults which are detected during motor stopped,
e.g. undervoltage happens while motor is
stopped or an external trip (through DI) which is
received during motor stopped. The relay remains
activated while motor is at fault and will not
recovered until the trip source is removed. The
relay is configurable as energized type or de-
energized type.
Specific trip function:
The output can be assigned with specific trip
function including TOL, Earth fault trip, Stalled
rotor trip, Phase failure trip. Phase unbalance trip,
Under-load trip, No-load trip, PTC trip, Under-
voltage trip, Start limitation trip, Long start trip,
Phase sequence trip.
Alarms:
This is a general alarm function. The relay is
energized or de-energized whenever an alarm
occurs.
Specific alarm function:
The output can be assigned with specific alarm
function including TOL, Earth fault alarm, over-
load alarm, Phase failure alarm. Phase unbalance
alarm, Under-load alarm, No-load Alarm, PTC
alarm, PTC short circuit alarm, PTC open circuit
alarm, Under-voltage alarm, Start limitation
alarm, Under-voltage alarm, Auto-reclose alarm.
Watchdog output:
M10x has an internal hardware watchdog
supervising the behavior of the microprocessor
software. Digital output can be used as signaling
output relay for indicating the status of the unit’s
internal watchdog.
Communication failure:
When a failure occurs, the relay can be set to
energized or de-energized via parameterization.
Contactor welded:
When contactor welded occurs, the relay can be
set to energized or de- energized via
parameterization.
RCU mode (M101 only):
This definition is assigned to the programmable
output when NR DOL/RCU, REV DOL/RCU or
contactor feeder/RCU is selected as the motor
start mode. The relay output serves the same
function of de-energizing the contactor coil as
CCC output in M102.
Local_remote output:
The relay is energized when the control authority
is remote only. The relay will be de-energized
when the control authority is local.
Ready to start:
The relay will energized when the module is not at
fault, not running and ready for a start.