106 Troubleshooting
31 MCU connection The inverter has diagnosed an internal communication error.
Power down the inverter.
Restart the inverter.
If the inverter returns to the same fault state, power down the
inverter and contact your system supplier.
32 MCU UAC The inverter has diagnosed an internal measurements
redundancy fault.
Power down the inverter.
Restart the inverter.
If the inverter returns to the same fault state, power down the
inverter and contact your system supplier.
33 MCU IGND The inverter has diagnosed an internal measurements
redundancy fault.
Power down the inverter.
Restart the inverter.
If the inverter returns to the same fault state, power down the
inverter and contact your system supplier.
34 DC input wiring The inverter has diagnosed a reverse polarity or short circuit at DC
terminals.
From Events menu
-
>
warnings, check if warning 1000 is also
active. If it is, check and replace all faulty string fuses.
Power down the inverter. Open the bottom cover and check that
all of the DC connectors are firmly in their correct positions in
accordance with the cable markings.
If no input connection errors are found, replace the bottom cover
and restart the inverter.
If cable markings are unclear or missing, or if the inverter returns
to the same fault state, power down the inverter and contact your
system supplier. Request a service visit to check the polarity and
order of DC input connectors, and to check the PV system
installation for short circuits and connection errors.
36 SW internal An illegal SW function was detected.
Try to reset the fault and monitor whether or not the inverter
returns to normal operation.
If the inverter does not return to normal operation, power down the
inverter and contact your system supplier.
Fault
message
ID code
Fault message
description
Causes of fault and corrective actions

Table of Contents

Other manuals for ABB PVS300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PVS300 and is the answer not in the manual?

ABB PVS300 Specifications

General IconGeneral
BrandABB
ModelPVS300
CategoryInverter
LanguageEnglish

Related product manuals