EasyManuals Logo
Home>ABB>Inverter>PVS300

ABB PVS300 User Manual

ABB PVS300
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #115 background imageLoading...
Page #115 background image
Technical data 115
Environmental data and requirements
Recommended tripping curve type of
external circuit breaker
Type B
Minimum / (maximum) allowed
nominal current rating of external
circuit breaker
20 A /
(63 A)
25 A /
(63 A)
25 A /
(63 A)
32 A /
(63 A)
50 A /
(63 A)
Inrush current 0 A (Inverter modulates and synchronizes in phase
before connection to grid)
Maximum fault current 87 A peak, 3-cycle RMS <9.5 A
Source: 3AXD00000593935, 3AXD10000042487
Inverter type PVS300-TL- 3300W-2 4000W-2 4600W-2 6000W-2 8000W-2
Environmental category Outdoor, wet locations
Ingress protection class IP55
Pollution degree classification PD3
Ambient temperature range allowed
during operation
-25 … +60 °C (-13 … +140 °F)
Maximum ambient temperature for
nominal power output
+ 50 °C (+122 °F)
In the ambient temperature range of 50…60 °C
(122…140 °F), the output current is decreased
according to temperature rise rate inside the inverter.
Ambient temperature range allowed
during storage and transportation
-40 … +70 °C (-40 … +158 °F)
Relative humidity level allowed, not
condensing
0…100%
Maximum installation altitude above
sea level
< 2000 m
Noise emissions
(at the operator’s position):
Values determined according to standards IEC62109-1,
ISO4871 and noise test code given in ISO3746.
Note: The declared single-number noise emission
values are the sum of measured values and the
associated uncertainty. They represent upper
boundaries of the range of values which are likely to
occur in measurements. The measurement distance
was 1 m and the following operating conditions were
applied for each inverter type: 720 VDC, 230 VAC,
50 Hz, nominal power output, cooling fans running.
A-weighted Sound pressure level <38 dBA <54 dBA
A-weighted Sound power level <51 dBA <67 dBA
Source: 3AXD00000593935, 3AXD10000042487, 3AXD10000077285
Inverter type PVS300-TL- 3300W-2 4000W-2 4600W-2 6000W-2 8000W-2

Table of Contents

Other manuals for ABB PVS300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PVS300 and is the answer not in the manual?

ABB PVS300 Specifications

General IconGeneral
BrandABB
ModelPVS300
CategoryInverter
LanguageEnglish

Related product manuals