Electrical installation 67
Note: Grounding the cable shield:
• Do not connect the cable shield to the isolated functional ground of terminals X2,
X3 or X4.
• Connect the cable shield with the provided clamp connectors to the grounded nut
insert [item 9].
• Ground only one end of the cable shield to avoid forming ground loops. Ground
loops can cause interference to the inverter’s operation.