1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 117
32 - Supplemental settings
From the service connector (with Ekip Connect) or with system bus communication it is also
possible to access parameters and commands that are not available directly from the display.
Below is a list and description of the various functions.
Sixteen independent programmable states are available, distinguished by the letters A, B, C, D,
E, F, G, H, I, L, M, N, O, P, Q, R, which allow different event control solutions.
Each programmable state can have two values: True or False, and several configuration
parameters are available:
Trigger: event or combination of multiple events (up to 24, in logical AND or OR
configuration) of state activation
On Delay: state activation delay, calculated starting from the presence of the trigger
Off Delay: state deactivation delay, calculated from when the trigger no longer exists
NOTE: the status is activated if the trigger is present for a time set in On Delay and is
deactivated if the trigger is absent for a time longer than the Off Delaysetting
The states can be used with the external Ekip Signaling 10K module, on Link Bus or with the
programmable functions to return the desired signal combination to contacts.
If present the external neutral V0 can be activated a measure filter (V0 filter):
If the filter is activated, the measurements and the specific protections are treated differently:
Ekip Touch applies a pass-band filter on the signal to measure only the basic component (50 or
60 Hz).
User-programmable labels useful for facilitating the remote identification of units;
NOTE: the TAG Name label and the communication address make up the identifier
used by Ekip Connect for the connected devices
Trigger Status
Programmable
States
TRUE
FALSE