1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 121
Additional functions
34 - Power Controller
Description
The Power Controller function allows managing the loads of a system according to the power
absorbed to reduce consumption and optimize energy efficiency.
All the parameters and measurements of the function are available via Ekip Connect, while the
Trip unit allows setting and viewing some of them, as noted below.
Ekip Touch
Parameters
Some function configuration parameters are available In the Settings - Power Controller menu
(page 29).
Parameter
Description
Default
Enable
Enable/disable the function and the availability of the parameters in
the menu
OFF
Load
Operating
Mode
Allows setting the configuration of each of the 15 programmable
loads (from Load 1 to Load 15). It is possible to choose between
Automatic or Manual configuration
Manual
Powers
Limits
Allows setting the 10 power limits (from Power Limit 1 to Power
Limit 10). The value is expressed in kW and can be set in a range
of: 10 kW .. 10000 kW with 10 kW steps.
10 kW
NOTE: to set all the parameters of the function it is recommended to first configure the
parameters via Ekip Connect, and only then work on the Trip unit to enable or change
loads and power limits
Ekip Touch
Measurements
In the summary pages, with Power Controller activated the specific page with the main
measurements is available:
Measurement
Description
Ea
Expected energy
T
Time spent within the evaluation window
LOADS
Number of controlled loads
LOADS Shed
Number of loads shed
With Power Controller activated, the Power Controller menu is available in the Information page
(page 30), and it provides information on the 15 loads in 2 submenus:
Submenu
Information included
Load Input Status
Load status (from Load 1 to Load 15): open or closed
Active load
Load configuration (from Load 1 to Load 15): active or inactive

Table of Contents

Other manuals for ABB SACE Tmax XT2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Tmax XT2 and is the answer not in the manual?

ABB SACE Tmax XT2 Specifications

General IconGeneral
BrandABB
ModelSACE Tmax XT2
CategoryCircuit breakers
LanguageEnglish

Related product manuals