1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 17
8 - Maintenance and malfunction identification
Introduction
The correct maintenance of the unit and connected devices ensures proper operation over time.
Maintenance operations must be carried out by expert personnel (see "Recipients” on page 4) in
accordance with safety regulations (see “Safety requirementson page 5) and the maintenance
program.
If there are anomalies or malfunctions it is necessary to identify the cause and eliminate it before
continuing use of the unit.
CAUTION! The identification of malfunctions must be done only by expert
electricians (IEV 195-04-01: person with relevant education and experience to
enable him or her to perceive risks and to avoid hazards which electricity can
create). In fact, it may be necessary to carry out isolation and dielectric tests on
a part or all of the installation.
Checks and
general cleaning
Perform the following checks:
1. Make sure Ekip Touch is clean, removing dust and any traces of other materials using dry,
clean rags (if necessary use mild detergents; for excessive dirt a laminate thinner like
Henkel 273471 or Chemma 18 or equivalent can be used).
2. Make sure that there are no foreign objects near connectors or terminals.
Check
Ekip Touch
Perform the checks listed in the chapter Startup on page 14, also checking the status of wiring
and accessory modules:
Alarm check
Check for presence and connection of modules (internal and external)
Check zone selectivity connections
Check the MOE-E energy storage controller
Check AUP circuit breaker status, for the removable version of the CB
NOTE: the limitations and the notes for each point in the respective paragraphs are valid
Maintenance
program
The Ekip Touch maintenance program is carried out with varying frequency depending on the
installation environment:
Standard environments
Dusty environments
(measured dust level > 1 mg/m3)
Maintenance
frequency
One year or 2000 maneuvers or
after a short circuit
Six months or 1000 maneuvers or
after a short circuit

Table of Contents

Other manuals for ABB SACE Tmax XT2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Tmax XT2 and is the answer not in the manual?

ABB SACE Tmax XT2 Specifications

General IconGeneral
BrandABB
ModelSACE Tmax XT2
CategoryCircuit breakers
LanguageEnglish

Related product manuals