1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 191
57 - Ekip Com IEC 61850
Ekip Com IEC 61850 is a communication accessory that enables Ekip Touch to be integrated
into an Ethernet network with IEC 61850 communication protocol, with remote supervision and
control functions.
The module is configured as master and from remote it is possible to
read information and Ekip Touch measurements
manage certain commands, including opening and closing actuator (MOE-E)
access to information and parameters that are not available on the display
supply vertical communication (reports) to higher supervision systems (SCADA), with
statuses and measurements (retransmitted each time and only if they are different from the
previous report)
supply horizontal communication (GOOSE) to other actuator devices (e.g.: medium voltage
switches), with all information on status and measurements normally shared by Ekip Com
communication modules on bus.
NOTE: the remote open and close commands to the switch can be run only if Ekip
Touch is in Remote configuration
To map the module in its communication network, the document System Interface is available
(page 128) that lists the necessary communication and command details.
The document also describes configuration files for protocol IEC 61850 and relative loading
procedure for assigning the Technical Name and any GOOSE enabling (by setting relative MAC
Addresses)
Depending on the parameters set, which are illustrated on subsequent pages, the following
module ports are used:
ISO Transport Service on top of the TCP (RFC 1006)
NTP - Network Time Protocol
TFTP - Trivial File Transfer Protocol
IMPORTANT: each XT2 / XT4 circuit breaker can accommodate only one module;
configuration with external communication modules is not permitted if an internal
module is present