1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 134
41 - Ekip Com Profibus DP
Ekip Com Profibus DP is a communication accessory that enables Ekip Touch to be integrated
into a RS-485 network with Profibus communication protocol, with remote supervision and control
functions.
The module is configured as Slave and from remote it is possible to:
read information and Ekip Touch measurements
manage certain commands, including opening and closing actuator (MOE-E)
access to information that is not available on the display
if connected to a withdrawable circuit-breaker, check the status of inserted / extracted
NOTE: the remote open and close commands to the switch can be run only if Ekip
Touch is in Remote configuration
To map the module in its communication network, the document System Interface is available
(page 128) that lists the necessary communication and command details.
To connect Ekip Com Modbus RTU to Ekip Touch, the Ekip Cartridge (page 129) and Ekip Supply
(page 130) accessories are required.
Ekip Touch can be configured with two different modules that are compatible with the Profibus
protocol: Ekip Com Profibus DP and Ekip Com Profibus DP Redundant.
The two modules are identical in terms of characteristics and installation methods, except for:
display menus on unit, cablings and addresses for external communication, that are specific for
each model.
NOTE: if not specified, the information in the following chapter applies to both models
Both modules can be connected simultaneously to Ekip Touch to increase the potential of unit
(for example: for applications in which great network reliability is necessary).
IMPORTANT: in each Ekip Touch can be installed only one module per type; it is
not admitted the connection of two equal modules (for example: two Ekip Com
Profibus DP Redundant)
Consult:
the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
The connections must be made with Belden 3079A or equivalent cables.
the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and
Ekip Touch.
Ekip Com Profibus DP is supplied directly by the Ekip Supply module, to which it is connected.
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted