1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 103
28 - Class 1 Power & Energy Metering
List and actions
The Class 1 Power & Energy Metering package allows obtaining higher measurement accuracy
for the following dimensions:
Measurement
Measurement range
(min-max)
Normal operating
range
Accuracy of
detected value
Phase currents
0.03 .. 64 In
IEC61557-12 standard,
tables 20-22
0.5%
(1)
Ground fault current
(2)
0.08 .. 64 In
IEC61557-12 standard,
table 20
0.5%
(1)
Grid frequency
30 .. 80 Hz
(3)
fn ± 10 %
(4)
± 0.02 Hz
Total active and
apparent power
|Pmin ..Pmax|
(5)
IEC61557-12 standard,
tables 8-11-14
1%
(1)
Active and apparent
phase power
|Pmin .. Pmax|
(5)
IEC61557-12 standard,
tables 8-11-14
1%
(1)
Total active and
apparent energy
1 kWh .. 2 TWh;
1 kVARh .. 2 TVARh;
1 kVAh .. 2 TVAh
IEC61557-12 standard,
tables 8-11-14
1%
(1)
Power Factor
0.5 .. 1
IEC61557-12 standard,
table 27
1%
(1)
NOTES:
(1) accuracy refers to normal operating ranges and conditions according to IEC
61557-12, for each declared dimension and class
(2) Available with LSIG versions
(3) Available for voltages greater than 30 V (with Un < 277 V) or 60 V (with Un
277 V)
(4) 45 .. 55 Hz with fn = 50 Hz; 54 .. 66 Hz with fn = 60 Hz
(5) Pmin = 0.5 In x 5 V; Pmax = 3 x 16 In x 690 V
Functional
characteristics
The measurement performance of the Class 1 Power & Energy Metering package are
guaranteed in the following conditions (from table 43 of the IEC61557-12 standard):
Feature
Value
Measurement device classification (PMD)
according to chapter 4.3 of the standard
PMD-DD
Temperature
Operating: T= -25 °C .. +70 °C;
Storage: T = -30 °C .. +70 °C;
Class: K70
Humidity and altitude
Relative humidity up to 90% without
condensation; from 0 to 2000 meters
Performance class for power and active energy
1
Information page
The Class 1 Power & Energy Metering package activates the information page IEC61557-12,
which can be viewed in the Information menu (page 30).
The page shows the activation status of the Class 1 Power & Energy Metering package
(Active/Inactive) and the serial numbers of some accessories mounted on the CB specifically to
respond to the characteristics of the package (assembly of electronic units and internal current
sensors)

Table of Contents

Other manuals for ABB SACE Tmax XT2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Tmax XT2 and is the answer not in the manual?

ABB SACE Tmax XT2 Specifications

General IconGeneral
BrandABB
ModelSACE Tmax XT2
CategoryCircuit breakers
LanguageEnglish

Related product manuals