Chapter 3
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018 339
Parameter Limitations
WNotch second order
LowLimit
WNotch fourth order
LowLimit
HighLimit
QFactor LowLimit = 0.5
HighLimit = 100.0
Whenever the value computed for the output is invalid, NAN, or INF, the
instruction sets Out = the invalid value. When the value computed for the output
becomes valid, the instruction initializes the internal parameters and sets Out =
In.
Affects Math Status Flags
No
Major/Minor Faults
None specific to this instruction. See Common Attributes for operand-related
faults.
Execution
Function Block
Condition/State Action Taken
Prescan EnableIn and EnableOut bits are cleared to false.
Tag.EnableIn is false EnableIn and EnableOut bits are cleared to false.
Tag.EnableIn is true EnableIn and EnableOut bits are set to true.
The instruction executes.
Instruction first run N/A
Instruction first scan Recalculate coefficients.
Postscan EnableIn and EnableOut bits are cleared to false.
Structured Text
Condition/State Action Taken
Prescan See Prescan in the Function Block table.
Normal Execution See Tag.EnableIn is true in the Function Block table.
Postscan See Postscan in the Function Block table.

Table of Contents

Other manuals for Allen-Bradley LOGIX 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley LOGIX 5000 and is the answer not in the manual?

Allen-Bradley LOGIX 5000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelLOGIX 5000
CategoryController
LanguageEnglish

Related product manuals