482 Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
See also
Attach to Equipment Sequence on page 465
Equipment Sequence Instructions on page 465
When a tag is assigned to store the result of an Equipment Sequence Clear Failure
(SCLF) instruction, the instruction returns one of the following codes when it
executes.
Code (Dec) Description
0 The command was successful.
48 The command was not executed because it was not possible at the time to generate an event to record the
command.
• If the command was an ABORT command, the ABORT command is still executed even if the event could not be
generated.
• This code only occurs if event generation has been enabled in the Equipment Sequence Properties -
Configuration tab.
24578 The command is not valid for the current state of the Equipment Sequence. For example, if the Equipment Sequence
is stopped, then a stop command is not valid.
24594 The Equipment Sequence is unscheduled, inhibited, or in a task that is inhibited.
Use the Result operand to get a code that shows the success or failure of the SCLF
instruction. The Result operand should contain either 0 or a DINT tag,
depending on whether ownership conflicts or other errors are likely to occur.
• If ownership conflicts or other errors are not likely, enter 0 in the Result
operand.
• If ownership conflicts or other errors are likely, enter a DINT tag in
the Result operand. The DINT tag stores a code for the result of the
execution of the instruction.
See also
Equipment Sequence Clear Failure on page 471
Equipment Sequence Instructions on page 465
instructions