Timer and Counter Instructions
Chapter 5
513
Figure 5.10
UpDown
Counter Example
||
00
(
CTU )
110 046
PR 220
AC 1
14
||
02
( CTD )
110 046
PR 220
AC 1
14
||
03
( CTR )
110 046
PR 220
AC 1
14
UpCount Event
DownCount Event
Counter Reset Event
NOTE: Bit 14 of the Accumulated Value word is set on when the
Accumulated Value either overflows or underflows. When a
Down-Counter Preset is set to 000, underflow bit 14 is not set on when the
count goes below zero.
When used alone, the CTD accumulated value may need to be reset in the
program to its original value (usually a value other than 000). For this
reason, a Get/Put transfer (Section 6.1), rather than a CTR instruction, is
usually used to load a value in the CTD Accumulated Value word. Get/Put
instructions are discussed in Section 6.1.
This output instruction is similar to a standard counter instruction. During
a true rung condition, the Accumulated Value is incremented once per
program scan (Figure 5.11). Unlike counters, however, the scan counter
does not count past the preset and resets when the rung goes false, power is
lost or the keyswitch is turned to program mode.
Figure 5.11
Scan
Counter Instruction
||
03
( SCT )
113 053
PR 700
AC 359
5.2.4
Scan Counter Instruction
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PLC-2/30 and is the answer not in the manual?

Allen-Bradley PLC-2/30 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPLC-2/30
CategoryController
LanguageEnglish

Related product manuals