Data Transfer File Instructions
Chapter 12
1218
Figure 12.16
FILETOWORD
MOVE Example Rung
FILE-TO-WORD
MOVE
COUNTER ADDR:
200
POSITION: 005
FILE LENGTH: 010
FILE A: 474-505
WORD ADDRESS:
400
200
(DN)
15
This output instruction transfers a duplicate of the value in a specified data
table word W (Figure 12.17) into a word in file R that is pointed to by the
counter accumulated value.
Instruction overview:
Output instruction
Key sequence: [FILE] 11
Requires 4 words of user program
Counter must be externally indexed by program
12.4
WordtoFile
Move
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com