Fuses and Circuit Breakers 2-85
Table 2.R PF700 208/240 Volt AC Input Recommended Protection Devices
Table 2.S PF700 400/480 Volt AC Input Recommended Protection Devices
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection.
(3)
Circuit Breaker - inverse time breaker.
(4)
Motor Circuit Protector - instantaneous trip circuit breaker.
(5)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(6)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on
480V or 600V Delta/Delta systems.
(7)
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001B-EN-P.
Drive
Catalog
Number
Frame
HP
Rating
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Non-Time
Delay Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(4)
140M Motor Starter with Adjustable Current Range
(5)(6)
ND HD Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
Min.
(1)
Max.
(2)
Amps Amps Available Catalog Numbers
(7)
208 Volt AC Input
20BB2P2 0 0.5 0.33 1.9 0.7 2.5 2.7 3.7 3 6 3 10 15 3 140M-C2E-B25 140M-D8E-B25 – –
20BB4P2 0 1 0.75 3.7 1.3 4.8 5.5 7.4 6 10 6 17.5 15 7 140M-C2E-B63 140M-D8E-B63 – –
20BB6P8 0 2 1.5 6.8 2.4 7.8 10.3 13.8 10 15 10 30 30 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
20BB9P6 0 3 2 9.5 3.4 11 12.1 16.5 12 20 12 40 40 15 140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 –
20BB015 1 5 3 15.7 5.7 17.5 19.2 26.2 20 35 20 70 70 30 140M-C2E-C20 140M-D8E-C20 140M-F8E-C20 –
20BB022 1 7.5 5 23.0 8.3 25.3 27.8 37.9 30 50 30 100 100 30 140M-C2E-C25 140M-D8E-C25 140M-F8E-C25 140M-CMN-2500
20BB028 2 10 7.5 29.6 10.7 32.2 37.9 50.6 40 70 40 125 125 50 – – 140M-F8E-C32 140M-CMN-4000
20BB042 3 15 10 44.5 16.0 48.3 53 72.5 60 100 60 175 175 70 – – 140M-F8E-C45 140M-CMN-6300
20BB054 3 20 15 57.2 20.6 62.1 72.5 97 80 125 80 225 225 100 – – – 140M-CMN-6300
240 Volt AC Input
20BB2P2 0 0.5 0.33 1.7 0.7 2.2 2.4 3.3 3 6 3 10 15 15 140M-C2E-B25 140M-D8E-B25 – –
20BB4P2 0 1 0.75 3.3 1.4 4.2 4.8 6.4 5 8 5 15 15 15 140M-C2E-B63 140M-D8E-B63 – –
20AB6P8 0 2 1.5 5.9 2.4 6.8 9 12 10 15 10 25 25 25 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
20BB9P6 0 3 2 8.3 3.4 9.6 10.6 14.4 12 20 12 35 35 35 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
20BB015 1 5 3 13.7 5.7 15.3 17.4 23.2 20 30 20 60 60 60 140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 –
20BB022 1 7.5 5 19.9 8.3 22 24.2 33 25 50 25 80 80 80 140M-C2E-C25 140M-D8E-C25 140M-F8E-C25 140M-CMN-2500
20BB028 2 10 7.5 25.7 10.7 28 33 44 35 60 35 100 100 100 – – 140M-F8E-C32 140M-CMN-4000
20BB042 3 15 10 38.5 16.0 42 46.2 63 50 90 50 150 150 150 – – 140M-F8E-C45 140M-CMN-6300
20BB054 3 20 15 49.5 20.6 54 63 84 70 100 70 200 200 200 – – – 140M-CMN-6300
Drive
Catalog
Number
Frame
kW/HP
Rating
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Non-Time
Delay Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(4)
140M Motor Starter with Adjustable Current Range
(5)(6)
ND HD Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
Min.
(1)
Max.
(2)
Amps Amps Available Catalog Numbers
(7)
400 Volt AC Input
20BC1P1 0 0.37 0.25 1.08 0.75 1.3 1.4 1.9 3 3 3 5 15 3 140M-C2E-B16 – – –
20BC2P1 0 0.75 0.55 1.7 1.2 2.1 2.4 3.2 3 6 3 8 15 3 140M-C2E-B25 140M-D8E-B25 – –
20BC3P5 0 1.5 0.75 3.1 2.1 3.5 4.5 6.0 6 8 6 12 15 7 140M-C2E-B40 140M-D8E-B40 – –
20BC5P0 0 2.2 1.5 4.5 3.2 5.0 5.5 7.5 6 10 6 20 20 7 140M-C2E-B63 140M-D8E-B63 – –
20BC8P7 0 4 2.2 8.2 5.7 8.7 9.9 13.2 15 17.5 15 30 30 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
20BC011 0 5.5 4 11.0 7.6 11.5 13 17.4 15 25 15 45 45 15 140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 –
20BC015 1 7.5 5.5 15.1 10.4 15.4 17.2 23.1 20 30 20 60 60 20 140M-C2E-C20 140M-D8E-C20 140M-F8E-C20 –
20BC022 1 11 7.5 21.9 15.2 22 24.2 33 30 45 30 80 80 30 140M-C2E-C25 140M-D8E-C25 140M-F8E-C25 –
20BC030 2 15 11 30.3 21.0 30 33 45 40 60 40 120 120 50 – – 140M-F8E-C32 –
20BC037 2 18.5 15 37.7 26.1 37 45 60 50 80 50 125 125 50 – – 140M-F8E-C45 –
20BC043 3 22 18.5 44.1 30.6 43 56 74 60 90 60 150 150 80 – – – –
20BC056 3 30 22 57.9 40.1 56 64 86 75 120 75 200 200 80 – – – –
480 Volt AC Input
20BD1P1 0 0.5 0.33 0.9 0.7 1.1 1.2 1.6 3 3 3 4 15 3 140M-C2E-B16 – – –
20BD2P1 0 1 0.75 1.6 1.4 2.1 2.4 3.2 3 6 3 8 15 3 140M-C2E-B25 – – –
20BD3P4 0 2 1.5 2.6 2.2 3.4 4.5 6.0 4 8 4 12 15 7 140M-C2E-B40 140M-D8E-B40 – –
20BD5P0 0 3 2 3.9 3.2 5.0 5.5 7.5 6 10 6 20 20 7 140M-C2E-C63 140M-D8E-C63 – –
20BD8P0 0 5 3 6.9 5.7 8.0 8.8 12 10 15 10 30 30 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
20BD011 0 7.5 5 9.5 7.9 11 12.1 16.5 15 20 15 40 40 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
20BD014 1 10 7.5 12.5 10.4 14 16.5 22 17.5 30 17.5 50 50 20 140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 –
20BD022 1 15 10 19.9 16.6 22 24.2 33 25 50 25 80 80 30 140M-C2E-C25 140M-D8E-C20 140M-F8E-C25 140M-CMN-2500
20BD027 2 20 15 24.8 20.6 27 33 44 35 60 35 100 100 50 – – 140M-F8E-C32 140M-CMN-4000
20BD034 2 25 20 31.2 25.9 34 40.5 54 40 70 40 125 125 50 – – 140M-F8E-C45 140M-CMN-4000
20BD040 3 30 25 36.7 30.5 40 51 68 50 90 50 150 150 50 – – 140M-F8E-C45 140M-CMN-4000
20BD052 3 40 30 47.7 39.7 52 60 80 60 110 60 200 200 70 – – – 140M-CMN-6300