EasyManuals Logo

Carrier AquaForce 30XBE 250 User Manual

Carrier AquaForce 30XBE 250
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
51
6 - APPLICATION DATA
6.1 - Operating range
Evaporator Leaving Water Temperature (°C)
Air inlet temperature (°C)
Low brine
Medium brine
Light brine
NOTE
Ranges given as a guide using ethylene glycol for an evaporator ΔT = 3K. Refer
to the electronic catalogue.
Winter operation option (included in standard for 30XBE & 30XBP ranges)
Low temperature brine, (-15°C ethylene glycol / -10°C propylene glycol)
Medium temperature brine, (-12°C ethylene glycol / -8°C propylene glycol)
Light temperature brine, (-3°C ethylene glycol / 0°C propylene glycol)
Full load - 30XB- range
Full load - 30XBE/P ranges
Full load - OPT 15LS(+)
Part load
Power factor correction option (option/QM 231) available for an inlet air
temperature up to +45°C
For operation in pure water at an inlet air temperature below 0°C, the frost
protection (option_41A or 41B) must be provided
ATTENTION: Option 28 (Winter operation)
If the outside temperature is below -10 °C and the unit has
been switched o for more than 4 hours, it is necessary to
wait 2 hours after the unit has been switched on again to allow
the frequency converter to warm up.
Water heat exchanger Minimum Maximum
Entering temperature at start-up °C - 45
(1)
Leaving temperature during operation °C 3,3 15
Entering/leaving water temperature
di󰀨erence
K 2,8 10
Condenser air temperature Minimum Maximum
Storage -20 68
Operation, standard unit -10 55
(2)
With winter operation option (option 28) -20 55
(2)
With Low noise option (option 15LS) -10 52
(2)
Note: If the air temperature is below 0°C, a glycol/water solution or the frost
protection option must be used.
Note: If the leaving water temperature is below 4°C, a glycol/water solution or
the frost protection option must be used.
(1) Based on the installation type and the air temperature
(2) Part load, depended of sizes & leaving water temperature
6.2 - Minimum chilled water ow (units without
hydraulic module)
The minimum chilled water ow is shown in the table on the next
page. It is determined in order to allow su󰀩cient exchange and
preent the risk of excessive fouling. If the system ow is less than
this, the evaporator ow can be recirculated, as shown in the
diagram.
For minimum chilled water ow rate
1
2
1 Evaporator
2 Recirculation
6.3 - Maximum chilled (units without hydraulic
module)
The maximum chilled water ow is shown in the table on the next
page. If the system ow exceeds the maximum value, it can be
bypassed as shown in the diagram.
For maximum chilled water ow rate
1
2
1 Evaporator
2 Bypass
6.4 - Variable ow evaporator
Variable evaporator ow can be used in standard 30XB(E/P)
chillers. The chillers maintain a constant leaving water temperature
under all ow conditions. For this to happen, the minimum ow
rate must be higher than the minimum ow given in the table of
permissible ow rates and must not vary by more than 10% per
minute.
If the ow rate changes more rapidly, the system should contain
a minimum of 6.5 litres of water per kW instead of 3.25 l/kW.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier AquaForce 30XBE 250 and is the answer not in the manual?

Carrier AquaForce 30XBE 250 Specifications

General IconGeneral
BrandCarrier
ModelAquaForce 30XBE 250
CategoryChiller
LanguageEnglish

Related product manuals