9.10 - Frost protection
The heat reclaim condenser is equippped with electric heaters to protect the condenser against frost. These are activated if the
condenser entering and leaving water tem-peratures are below 3 °C and deactivated, if they are higher than 4.3 °C.
10 - FANS WITH AVAILABLE PRESSURE (OPTION 10)
If this option has been selected, the fans with available pressure are equipped with discharge connection anges to facilitate the duct
connection.
NOTE: Each fan must be individually ducted.
9 - HEAT RECLAIM CONDENSER OPTION (OPTION 50)