– 17 –
1.SPECIFICATIONS
1-1. 208/230V model
Single unit (System with Non-ducted indoor units)
(*1) Rated conditions
Cooling : Indoor air temperature 80 °F DryBulb/67 °F WetBulb, Outdoor air temperature 95 °F DryBulb
Heating : Indoor air temperature 70 °F DryBulb, Outdoor air temperature 47 °F DryBulb/43 °F WetBulb
072,096 type :Equivalent piping length : 50ft , Hight difference : 0ft , 120 type :Equivalent piping length :
75ft , Hight difference : 0ft
Conditions based on Alternate Test Method guidelines provided by the U.S. Department of Energy(DOE)
(*2) Setting is necessary
(*3) The amount does not consider extra piping length. Refrigerant must be added on site in accordance with
the actual piping length.
(*4) High-pressure switch / High-pressure sensor / Low-pressure sensor / Fusible plug / PC board fuse /
Inverter overload protector
(*5) Select wire size based on the larger value of MCA.
MCA : Minimum Circuit Amps (minimum circuit Amps required for power supply design.)
(*6) MOCP : Maximum Overcurrent Protection(Amps)
Outdoor unit model name MMY- MAP0724FT9UL MAP0964FT9UL MAP1204FT9UL
(208 / 230) / 3 / 60V/Ph/HzCenter VoltagePower Supply
9672 120Nominal capacity (*1)
10881
kBtu/h
kBtu/h 135Nominal capacity
Cooling
Heating (*1)
Soft StartAStarting Current
76.376.3 76.3InHeight
Dimension
788616 788lbsPacked
Total Weight
Silky shade (Munsell 1Y8.5/0.5)Color
Hermetic twin rotary compressorType
Compressor
2.1 × 3 2.7 × 32.3 × 2kWMotor output
Propeller fanFan
1.0 1.01.0kWMotor outputFan unit
7,060 7,6205,120cfmAir volume
OFF:420 ON:540High-pressure switch psi
0.16 0.160.20In WG(*2)Maximum external static pressure
Finned tubeHeat exchanger
R410A
Refrigerant
Name
25.4 25.425.4lbs(*3)Charged refrigerant amount
751583 751lbsUnit
50.541.8 50.5InWidth
32.632.6 32.6InDepth
72.972.9 72.9InHeight
47.639.0 47.6InWidth
Packing
Unit
30.730.7 30.7InDepth
(*4)Protective devices
5034 52Electrical
specifications
Unit
MCA (*5) A
6040 60MOCP (*6) A
Refrigerant piping
1/2"1/2" 1/2"Diameter In
7/8"7/8" 1-1/8"Diameter In
3/4"3/4" 3/4"Diameter
Liquid
Suction gas
Discharge gas In
FlareType
Balance
3/8"3/8" 3/8"Diameter In
1612Maximum number of indoor unitsIndoor units 20
14 to 109Cooling
Operation temperature range
– 4 to 60Heating
FDB
FWB
62.0Cooling
Sound pressure level
63.0
56.0
58.0
63.5
65.5Heating
dB(A)
dB(A)
A value of the specifications list is numerical value
as of Jun., 2013 and may change it without a notice.