When binary output breaker close/open closes there is 2 sec delay for breaker fail detection.
Image 5.37 Breaker fail - breaker close/open closes
5.4.13 Exercise timers
The exercise (general-purpose) timers in controller areis intended for scheduling of any operations such as e.g.
periodic tests of the gen-set, scheduled transfer of the load to the gen-set prior to an expected disconnection of
the mains etc.
Related setpoints for timer 1 are:
Timer 1 Function (page 250)
Timer 1 Repetition (page 250)
Timer 1 First Occur. Date (page 251)
Timer 1 First Occur. Time (page 251)
Timer 1 Duration (page 251)
Timer 1 Repeated (page 252)
Timer 1 Repeat Day (page 254)
Timer 1 Day (page 254)
Timer 1 Repeated Day In Week (page 255)
Timer 1 Repeat Day In Month (page 255)
Timer 1 Repeat Week In Month (page 255)
Timer 1 Refresh Period (page 253)
Timer 1 Weekends (page 254)
Related setpoints for timer 2 are:
Timer 2 Function (page 257)
Timer 2 Repetition (page 257)
Timer 2 First Occur. Date (page 258)
Timer 2 First Occur. Time (page 258)
Timer 2 Duration (page 258)
Timer 2 Repeated (page 259)
Timer 2 Repeat Day (page 261)
Timer 2 Day (page 261)
Timer 2 Repeated Day In Week (page 262)
Timer 2 Repeat Day In Month (page 262)
Timer 2 Repeat Week In Month (page 262)
Timer 2 Refresh Period (page 260)
Timer 2 Weekends (page 261)