InteliMains 210 Global Guide
192
Group: Power Management
Subgroup: Power Management Control
Setpoint group Power Management Related FW 2.0.0
Range [units] ABS [kW] / REL [%]
Default value ABS Alternative config NO
Step [-]
Comm object 9874 Related applications MCB, MGCB
Description
This setpoint is used to select the Power management (page 78) mode.
ABS [kW]
The power management is based on actual active power and gen-set nominal power.
The reserves are calculated and adjusted in kW.
REL [%]
The power management is based on the relative load, i.e. ratio active power to nominal
power. The reserves are calculated and adjusted in %.
#Power Management Mode
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units] Disabled / Run Hours Equal / Efficient [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 10593 Related applications MCB, MGCB
Description
This setpoint adjusts priority auto swapping.
Disabled Optimalization is disabled.
Run Hours Equal
This method changes the priorities (not the setpoints itself) to equalize running
hours of the gen-sets or to keep constant difference of running hours by the
controller (adjusted via setpoint #Run Hours Max Difference (page 200)).
Efficient
This method changes the priorities (not the setpoints itself) to optimize which gen-
sets are running according to their capacities and actual load demand.
IMPORTANT: This priority swapping function is only for absolute
mode of power management (#Power Management Mode (page 192) =
ABS).
Optimal power band (number of running gen-sets) is calculated based on the
nominal power of each gen-set, their Run Hours and requested Load reserve. For
gen-sets with the same nominal power also run hour equalization is being
performed.
#Priority Auto Swap
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals