InteliMains 210 Global Guide
181
Setpoint group Engine settings Related FW 2.0.0
Range [units] 0 .. 600 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8383 Related applications MCB, MGCB, BTB
Description
Delay for Battery Undervoltage (page 180) and Battery Overvoltage (page 180) protection.
Battery <> Voltage Delay
6 back to List of setpoints
Group: Communication Settings
Subgroup: Controller CAN Address
Setpoint group
Communication
Settings
Related FW 2.0.0
Range [units] 1 .. 32 [-]
Default value 1 Alternative config NO
Step 1
Comm object 24537 Related applications MCB, MGCB, BTB
Description
Controller identification number. It is possible to set controller address different from the default value (1) so
that more controllers can be interconnected (via RS485) and accessed e.g. from MODBUS terminal.
Note: When opening connection to the controller it's address has to correspond with the setting in PC
tool.
Controller Address
6 back to List of setpoints
Subgroup: RS485 Settings
Setpoint group
Communication
Settings
Related FW 2.0.0
Range [units] Direct / MODBUS [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24134 Related applications MCB, MGCB, BTB
Description
Communication protocol switch for on-board RS485.
Direct InteliConfig communication protocol via serial cable.
MODBUS MODBUS protocol.
RS485 Mode
6 back to List of setpoints