Group: Basic settings
Subgroup: Name
Setpoint group Basic settings Related FW 2.0.0
Range [units] 0 .. 15 characters [-]
Default value InteliGen Alternative config NO
Step [-]
Comm object 8637 Related applications MCB, MGCB, BTB
Description
User defined name, used for the controller identification at remote phone or mobile connection. Gen-Set
Name is maximally 15 characters long and can be entered using InteliConfig or from controller’s
configuration menu.
Note: If the Gen-Set Name is "TurboRunHours", the running hours will be counted faster - 1 minute in
real will represent 1 hour.
Controller Name
6 back to List of setpoints
Subgroup: Power settings
Setpoint group Basic settings Related FW 2.0.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config Yes
Step 1 kW
Comm object 8276 Related applications MCB, MGCB, BTB
Description
Nominal power imported from the Bus. Bus Overload BOR protection is based on this setpoint.
Nominal Bus Import
6 back to List of setpoints
Subgroup: Current settings
Setpoint group Basic settings Related FW 2.0.0
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1 A
Comm object 8275 Related applications MCB, MGCB, BTB
Description
It is current limit for current protections and means maximal continuous current.
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Current 1 (page 295),
Nominal Current 2 (page 297) and Nominal Current 3 (page 299).
Nominal Current