Troubleshooting by Indication on the Remote Controller ESIE09-08B
152 Troubleshooting
3.16 “E4 Outdoor Unit: Actuation of Low Pressure Sensor
Remote Control
Display
E4
Applicable
Models
ER*Q 011~016*
Method of
Malfunction
Detection
Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Decision
Conditions
Error is generated when the low pressure is dropped under specific pressure.
Operating pressure: 0.07MPa
Supposed
Causes
Abnormal drop of low pressure (Lower than 0.07MPa)
Defect of low pressure sensor
Defect of outdoor unit PC board (A1P)
Stop valve is not opened.