ESIE09-08B Troubleshooting by Indication on the Remote Controller
Troubleshooting 171
3.30 “J6 Outdoor Unit: Malfunction of Thermistor (R6T) for
Outdoor Unit Heat Exchanger
Remote Control
Display
J6
Applicable
Models
ER*Q 011~016*
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Supposed
Causes
Defect of thermistor (R6T) for outdoor unit heat exchanger
Defect of outdoor unit PC board (A1P)
Troubleshooting
Refer to thermistor resistance / temperature characteristics table on P239.
Caution
Be sure to turn off power switch before connect or disconnect
connector, or parts damage may be occured.
(V3074)
NO
NO
Replace the thermistor (R6T).
YE S
YE S
Connect the thermistor and turn on again.
Connector
is connected
to X13A of outdoor unit
PC board (A1P)
Resistance
is normal when
measured after
disconnecting the thermistor
(R6T) from the outdoor
unit PC board.
(3.5kW~360kW)
Replace outdoor unit PC board (A1P).

Table of Contents

Other manuals for Daikin Altherma HT

Question and Answer IconNeed help?

Do you have a question about the Daikin Altherma HT and is the answer not in the manual?

Daikin Altherma HT Specifications

General IconGeneral
TypeAir-to-water heat pump
RefrigerantR-410A
Water Outlet TemperatureUp to 80°C
Operating Temperature Range-20°C to 35°C
Power Supply3-phase, 400V
Energy Efficiency Class (Heating)A++

Related product manuals