ESIE09-08B Precautions for New Refrigerant (R-410A)
Precautions for New Refrigerant (R-410A) 269
1.2 Refrigerant Cylinders
Cylinder specifications
The cylinder is painted refrigerant color (pink).
The cylinder valve is equipped with a siphon tube.
Handling of cylinders
(1) Laws and regulations
R-410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High-Press
ure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high-pressure gases. Be s
ure to follow the regulations.
(2) Handing of vessels
Since R-410A is high-pressure gas, it is contained in high-pressure vessels.
Although those vessels are durable and strong, careless handling can cause damage that
can lead to une
x
pected accidents. Do not drop vessels, let them fall, apply impact or roll
them on the ground.
(3) Storage
Although R-410A is not flammable, it must be stored in a well-ventilated, cool, and dark
place in the same
way as any other high-pres
sure gases.
It should also be noted that high-pressure vessels are equipped with safety devices that
releas
es gas when the ambient temperature reaches more than a certain level (fusible plug
melts) and when the pressure exceeds a certain level (spring-type safety valve operates).
Refrigerant can be charged in liquid state with cylinder in
upright position.
Caution: Do not lay cylinder on its side during charging, since
it cause refrigerant in gas state to enter the system.
Siphon tube
Cylinder

Table of Contents

Other manuals for Daikin Altherma HT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Altherma HT and is the answer not in the manual?

Daikin Altherma HT Specifications

General IconGeneral
TypeAir-to-water heat pump
RefrigerantR-410A
Water Outlet TemperatureUp to 80°C
Operating Temperature Range-20°C to 35°C
Power Supply3-phase, 400V
Energy Efficiency Class (Heating)A++

Related product manuals