10.3.3 Contactor
To remove or reinstall the contactor, use the following
steps. Refer to Illustration 10.33.
Disassembly
1. Remove the AC input busbars. Refer to
chapter 11.2.5 AC Input Busbars.
2. Remove fuses by removing 3 nuts (13 mm).
3. Remove the contactor coil wires from terminals
A1 and A2.
4. Remove the contactor by removing 4 bolts (13
mm) that attach the contactor to the contactor
bracket.
Reassembly
Reinstall in reverse order of this procedure. Tighten
hardware according to chapter 14.1 Fastener Torque Ratings.
10.3.4 Disconnect
To remove or reinstall the disconnect, use the following
steps. Refer to Illustration 10.33.
Disassembly
1. Remove the fuses. Refer to chapter 11.2.5 AC Input
Busbars.
2. Remove the air bae by removing 2 nuts (8 mm).
3. Remove 4 nuts (8 mm), 1 from each corner of the
disconnect.
4. Lift the disconnect from the drive.
Reassembly
Reinstall in reverse order of this procedure. Tighten
hardware according to chapter 14.1 Fastener Torque Ratings.
D1h/D3h/D5h/D6h/J8 Drive Di...
VLT
®
FC Series, D1h–D8h, Da2/Db2/Da4/Db4, E1h–E4h, J8/J9
182 Danfoss A/S © 02/2019 All rights reserved. MG94A502
1010

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals