4.2.1 Uploading Data to the LCP
1. Press [Off] to stop the motor before uploading or
downloading data.
2.
Go to 0-50
LCP Copy.
3. Press [OK].
4.
Select All to LCP.
5. Press [OK]. A progress bar shows the uploading
process.
6. Press [Hand On] or [Auto On] to return to normal
operation.
4.2.2 Downloading Data from the LCP
1. Press [Off] to stop the motor before uploading or
downloading
data.
2.
Go to 0-50
LCP Copy.
3. Press [OK].
4.
Select All from LCP.
5. Press [OK]. A progress bar shows the
downloading process.
6. Press [Hand On] or [Auto On] to return to normal
operation.
4.3 Restoring Default Settings
CAUTION
Initialisation restores the unit
to factory default settings.
Any programming, motor data, localization, and
monitoring records will be lost. Uploading data to the LCP
provides a backup before initialisation.
Restoring the frequency converter parameter settings back
to default values is
done by initialisation of the frequency
converter. Initialisation can be through 14-22 Operation
Mode or manually.
•
Initialisation using 14-22 Operation Mode does not
change frequency converter data such as
operating hours, serial communication selections,
personal menu settings, fault log, alarm log, and
other monitoring functions
•
Using 14-22 Operation Mode is generally
recommended
•
Manual initialisation erases all motor,
programming, localization, and monitoring data
and restores factory default settings
4.3.1 Recommended Initialisation
1. Press [Main Menu] twice to access parameters.
2.
Scroll to 14-22 Operation
Mode.
3. Press [OK].
4.
Scroll to Initialisation.
5. Press [OK].
6. Remove power to the unit and wait for the
display to turn off.
7. Apply power to the unit.
Default parameter settings are restored during start up.
This may take slightly longer than normal.
8. Alarm 80 is displayed.
9. Press [Reset] to return to operation mode.
4.3.2 Manual Initialisation
1. Remove power to the unit and wait for the
display
to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time and apply power to the unit.
Factory default parameter settings are restored during start
up. This may take slightly longer than normal.
Manual initialisation does not the following frequency
converter information
•
15-00 Operating Hours
•
15-03 Power Up's
•
15-04 Over Temp's
•
15-05 Over Volt's
User Interface
VLT
®
Decentral Drive FCD 302 Operating Instructions
36 MG04F302 - VLT
®
is a registered Danfoss trademark
44