DC voltage level 380-480 V units (V DC)
Inverter undervoltage
disable
373
Undervoltage warning 410
Inverter undervoltage re-
enable
(warning
reset)
398
Overvoltage
warning
(without
brake)
778
Dynamic brake turn
on 778
Inverter overvoltage re-
enable
(warning reset)
795
Overvoltage warning
(with
brake)
810
Overvoltage trip 820
Table 8.3 FCD 302 DC Voltage Level
Fuses
The unit is suitable
for use on a circuit capable of
delivering not more than 100,000 RMS symmetrical
Amperes, 480 V maximum.
Circuit breaker
The unit is suitable for use on a circuit capable of
delivering not more than 10,000 RMS symmetrical
Amperes, 480 V maximum.
Specifications
VLT
®
Decentral Drive FCD 302 Operating Instructions
76 MG04F302 - VLT
®
is a registered Danfoss trademark