8 Specifications
8.1 Electrical Data and Wire Sizes
Mains Supply 3x380-480 V AC
Frequency Converter PK37 PK55 PK75 P1K1 P1K5 P2K2 P3K0
Rated Shaft Output [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3.0
Rated Shaft Output [hp] 0.5 0.75 1.0 1.5 2.0 3.0 4.0
Max. input current
ON
WARNING
ALARM
Bus MS NS2NS1
130BB800.10
Continuous (3x380-440 V) [A] 1.2 1.6 2.2 2.7 3.7 5.0 6.5
Intermittent (3x380-440 V) [A] 1.9 2.6 3.5 4.3 5.9 8.0 10.4
Continuous (3x441-480 V) [A] 1.0 1.4 1.9 2.7 3.1 4.3 5.7
Intermittent (3x441-480 V) [A] 1.6 2.2 3.0 4.3 5.0 6.9 9.1
Recommended max. fuse size* gG-25
Built-in circuit breaker (large unit) CTI-25M Danfoss part no.: 047B3151
Recommended circuit breaker (small
unit) CTI-45MB Danfoss part no.: 047B3164
Power loss at max. load [W] 35 42 46 58 62 88 116
Efficiency 0.93 0.95 0.96 0.96 0.97 0.97 0.97
Weight, small unit [kg] 9.8 N/A
Weight, large unit [kg] 13.9
Output current
ON
WARNING
ALARM
Bus MS NS2NS1
130BB799.10
Continuous (3x380-440 V) [A] 1.3 1.8 2.4 3.0 4.1 5.2 7.2
Intermittent (3x380-440 V) [A] 2.1 2.9 3.8 4.8 6.6 8.3 11.5
Continuous (3x441-480 V) [A] 1.2 1.6 2.1 3.0 3.4 4.8 6.3
Intermittent (3x441-480 V) [A] 1.9 2.6 3.4 4.8 5.4 7.7 10.1
Continuous kVA (400 V AC) [kVA] 0.9 1.3 1.7 2.1 2.8 3.9 5.0
Continuous kVA (460 V AC) [kVA] 0.9 1.3 1.7 2.4 2.7 3.8 5.0
Max. cable size: (mains, motor,
brake)
[mm
2
/ AWG]
solid cable
6/10
flexible cable 4/12
Table 8.1 FCD 302 Shaft Output, Output Current and Input Current
*To meet UL/cULrequirements, use the following pre-fuses.
Recommended
maximum
pre-fuse
size
25 A
Brand Fuse Type UL File no. UL Category
(CCN code)
Bussmann FWH-25 E91958 JFHR2
Bussmann KTS-R25 E52273 RK1/JDDZ
Bussmann JKS-25 E4273 J/JDDZ
Bussmann JJS-25 E4273 T/JDDZ
Bussmann FNW-R-25 E4273 CC/JDDZ
Bussmann KTK-R-25 E4273 CC/JDDZ
Bussmann LP-CC-25 E4273 CC/JDDZ
SIBA 5017906-025 E180276 RK1/JDDZ
LITTLE FUSE KLS-R25 E81895 RK1/JDDZ
FERRAZ-
SHAWMUT
ATM-R25 E163267/
E2137
CC/JDDZ
FERRAZ-
SHAWMUT
A6K-25R E163267/
E2137
RK1/JDDZ
FERRAZ-
SHAWMUT
HSJ25 E2137 J/HSJ
Table 8.2 FCD 302 Pre-fuses Meeting UL/cUL Requirements
Specifications
VLT
®
Decentral Drive FCD 302 Operating Instructions
MG04F302 - VLT
®
is a registered Danfoss trademark
75
8 8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for Danfoss vlt fcd 302