Troubleshooting
Contact the local Danfoss supplier for advice.
There are no parameters relatedto this trip message.
11.2.55 Zero Speed Detect
Cause
The zero-speed detect input has not closed within the expected duration of a soft stop.
Troubleshooting
Check that the zero-speed sensor is operating correctly.
Check that parameter 2-17 Brake Current Limit and parameter 5-15 Excess Start Time are appropriate for the application.
Check the following parameters:
Parameter 2-17 Brake Current Limit.
Parameter 3-19 Brake Current Limit-2.
Parameter 5-15 Excess Start Time.
11.3 General Faults
See
Table 215 for situations where the soft starter does not operate as expected but neither trips nor issues a warning.
Table 215: General Faults
Symptom
Probable cause/suggested solution
"Not ready" on dis-
play
The reset input may be active. If the reset input is active, the soft starter does not operate.
Simul on display
The soft starter is running simulation software. This software is intended for demonstration purposes on-
ly and is not suitable for controlling a motor. Contact the local supplier for advice.
The soft starter does
not respond to the
[Hand on] and [Re-
set] keys.
The soft starter only accepts commands from the LCP if parameter 1-1 Command Source is set to Remote
LCP. Check that the Local LED on the soft starter is on.
The soft starter does
not respond to com-
mands from the con-
trol inputs.
The soft starter only accepts commands from the inputs if parameter 1-1 Command Source is set to
Digital Input. Check the setting of parameter 1-1 Command Source.
The control wiring may be incorrect. Check that the remote start, stop, and reset inputs are config-
ured correctly (see
5.4.3 Start/Stop) for details.
The signal to the remote inputs may be incorrect. Test the signaling by activating each input signal in
turn.
The soft starter does
not respond to a
start command from
either the LCP or the
digital inputs.
The soft starter may be waiting for the restart delay to elapse. Parameter 5-16 Restart Delay controls
the length of the restart delay.
The motor may be too hot to allow a start. The soft starter only allows a start when it calculates that
the motor has sufficient thermal capacity to complete the start successfully. Wait for the motor to
cool, before attempting another start.
The reset input may be active. If the reset input is active, the soft starter does not operate.
The soft starter may be waiting for control signals via the communications network (parameter 1-1
Command Source set to Network).
The soft starter may be waiting for a scheduled auto-start (parameter 1-1 Command Source set to
Clock).
Erratic and noisy mo-
tor operation
If the soft starter is connected to the motor using inside delta configuration, the soft starter may not be
detecting the connection correctly. Contact the local supplier for advice.
AQ262141844215en-000401 / 175R1174 | 129Danfoss A/S © 2020.12
Troubleshooting
VLT® Soft Starter MCD 600
Operating Guide

Table of Contents

Other manuals for Danfoss VLT MCD 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 600 and is the answer not in the manual?

Danfoss VLT MCD 600 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 600
CategoryController
LanguageEnglish

Related product manuals