3 cycle short cct rating @600 V AC
(1)
1
Suitable for use in a circuit with the prospective current noted, when protected by any listed fuses or listed circuit breakers sized according to the
NEC.
3.15.1.2 Models MCD6-0654B~MCD6-1250B & MCD6-0590C~MCD6-1134C
Suitable for use on a circuit capable of delivering up to the stated fault current, when protected by the specified circuit breaker, or
by a class L fuse sized according to the NEC.
These nominal ratings are based on start current of 300% FLC for 10 s for models MCD6-0654B~MCD6-1250B and start current of
300% at 50% duty for models MCD6-0590C~MCD6-1134C.
Table 19: Maximum Fuse Rating [A] - Standard Fault Short-Circuit Current
Fault current rating [kA]
3.15.2 High Fault Short-circuit Current Ratings
Suitable for use on a circuit capable of delivering up to the stated fault current, when protected by the specified circuit breaker, or
by a class L fuse sized according to the NEC.
These nominal ratings are based on start current of 300% FLC for 10 s.
Circuit breakers with model codes beginning with HFD/HJD/HKD/HLD are from Eaton.
Circuit breakers with model codes beginning with SELA/SFLA/SGLA are from GE.
Circuit breakers with model codes beginning with UTS are from LS Electric.
N O T I C E
Models MCD6-0160C~MCD6-0448C are not UL Listed.