1.
2.
3.
4.
5.
6.
7.
•
•
•
1.
2.
3.
6 Set-up Tools
6.1 Introduction
Set-up Tools includes options to load or save parameters to a backup file, set the soft starter's network address, check the status of
the inputs and outputs, reset the thermal models, or test operation using the Run Simulation.
To access Set-up Tools, press [Menu/Store] to open the Main Menu and then select Set-up Tools.
6.2 Setting Date and Time
Procedure
Press [Menu/Store] to open the menu.
Select Set-up Tools.
Scroll to Set Date & Time.
Press [Menu/Store] to enter edit mode.
Press [Menu/Store] and [Back] to select which part of the date or time to edit.
Press [▵] and [▿] to change the values.
Press [Menu/Store] after the last digit to save the setting.
When the action has been completed, the screen briefly shows a confirmation message, then returns to the previous menu level.
6.3 Command Source
Start and stop the soft starter via the digital inputs, remote LCP 601, communication network, smart card, or scheduled auto-start/
stop. Set up the command source via Set-up Tools or via parameter 1-1 Command Source.
If the remote LCP is installed, the [CMD/Menu] key provides shortcut access to the Command Source function in Setup Tools.
6.4 Commissioning
Commissioning allows starting and stopping the soft starter via the LCP. Press [▵] [▿] to select a function, then press [Menu/Store] to
send the selected command to the soft starter. The available functions are:
Quick stop (coast to stop)/reset.
Start.
Stop.
6.5 Run Simulation
The Run Simulation simulates a motor starting, running, and stopping to confirm that the soft starter and associated equipment
have been installed correctly.
N O T I C E
Disconnect the soft starter from mains voltage when using simulation mode.
The simulation is only available when the soft starter is in ready state.
Procedure
Press [Menu/Store] and select Setup Tools.
Scroll to Run Simulation and press [Menu/Store].
Apply a start command from the selected command source.
AQ262141844215en-000401 / 175R117448 | Danfoss A/S © 2020.12
Set-up Tools
VLT® Soft Starter MCD 600
Operating Guide