9.10 Pump Clean
The soft starter can perform a pump clean function before soft starting the motor. This can help dislodge debris from the impeller.
Pump clean starts the motor in reverse then forward direction, then stops the motor. Pump clean can be configured to repeat the
process up to 5 times. After the specified number of cleaning cycles, the soft starter performs the programmed soft start.
Pump clean operation is controlled by the start/stop input (START, COM+). Set a programmable input to pump clean (see parameter
7-1 Input A Function for details). Ensure that the input is closed when the start signal is applied.
Reverse torque/
Forward current (%FLC)
Illustration 38: Pump Clean
Parameter 11-1 Reverse Torque
Parameter 11-2 Reverse Time
Parameter 11-3 Forward Current Limit
Parameter 11-4 Forward Time
Parameter 11-6 Pump Stop Time
Parameter 11-7 Pump Clean Cycles
9.11 Reverse Direction Operation
The soft starter can control a reversing contactor to operate the motor in reverse direction. When reverse operation is selected, the
soft starter performs a soft start using the opposite phase sequence from normal operation.
Reverse operation is controlled by the start/stop input (START, COM+). Set a programmable input to reverse direction (parameter
7-1 Input A Function) and set an output to reversing contactor (parameter 8-1 Relay A Function).
The input must be closed when the start signal is applied. The soft starter keeps the reverse relay in the same state until the end of
the starting/stopping cycle.
The following example is a simple installation, but many different configurations are possible depending on the application require-
ments. Contact a local supplier for an application note showing more installation options.
N O T I C E
The first start after the direction is changed will be constant current.
N O T I C E
If phase sequence protection is required, install the reversing contactor on the output (motor) side of the soft starter.