3.14 IEC Coordination with Short-circuit Protection Devices
These fuses were selected based on a start current of 300% FLC for 10 s.
Table 15: Models MCD6-0020B~MCD6-0579B
Type 1 coordination 480 V AC, 65 kA
Bussmann NH fuse links
Type 2 coordination 690 V AC,
65 kA Bussmann DIN 43 653
Table 16: Models MCD6-0654B~MCD6-1250B/MCD6-0590C~MCD6-1134C, Bypassed Installation
Type 1 coordination 500 V AC,
100 kA
Type 2 coordination 690 V AC, 100 kA
AQ262141844215en-000401 / 175R117424 | Danfoss A/S © 2020.12
System Design
VLT® Soft Starter MCD 600
Operating Guide