Control voltage (soft starter)
Control voltage (external equipment)
Communications/smart card expansion port
Programmable input A (default = Input trip (N/O))
Programmable input B (default = Input trip (N/O))
Relay output A (default = Run)
Relay output B (default = Run)
5.10.2 Externally Bypassed Installation
The soft starter is installed with a main contactor (AC3-rated) and an external bypass contactor. To bypass the soft starter during
run, use an external bypass contactor with an AC1 rating. To bypass the soft starter completely (to allow direct on-line starting if the
soft starter is damaged), use an external bypass contactor with an AC3 rating.
Use the main contactor output (13, 14) to control the main contactor. Use the bypass contactor output (03, 04) to control the exter-
nal bypass.