Table 17: Models MCD6-0160C~MCD6-1134C, Continuous Connection
Nominal rating (A)
SCR I
2
t (A
2
s)
Type 1 coordination 500 V AC, 100
kA
Type 2 coordination 690 V AC, 100
kA
MCD6-0654B
190
320000
250NHG2B
170M3020
MCD6-0736B
260
315NHG2B
170M3021
MCD6-0950B
350
202000
355NHG2B
170M6009
MCD6-1154B
475
320000
425NHG2B
170M6010
MCD6-1250B
565
781000
630NHG3B
170M6011
MCD6-0590C
735
2530000
1000NHG4G
170M6016
MCD6-0667C
830
MCD6-0839C
1025
1200NHG4G
170M6017
MCD6-0979C
1170
3920000
OFAA5GG1250
Not available
MCD6-1134C
1220
7220000
170M6019
3.15 UL Coordination with Short-circuit Protection Devices
3.15.1 Standard Fault Short Circuit
3.15.1.1 Models MCD6-0020B~MCD6-0579B
Suitable for use on a circuit capable of delivering not more than the stated level of amperes (symmetrical rms), 600 V AC maximum.
These nominal ratings are based on a start current of 300% FLC for 10 s.
Table 18: Maximum Fuse Rating [A] - Standard Fault Short-Circuit Current
Model
Nominal rating [A]
3 cycle short cct rating @600 V AC
(1)
MCD6-0020B
24
5 kA
MCD6-0034B
42
MCD6-0042B
52
10 kA
MCD6-0063B
64
MCD6-0069B
69
MCD6-0086B
105
MCD6-0108B
120
MCD6-0129B
135
MCD6-0144B
184
18 kA
MCD6-0171B
225
MCD6-0194B
229
MCD6-0244B
250
MCD6-0287B
352
MCD6-0323B
397
AQ262141844215en-000401 / 175R1174 | 25Danfoss A/S © 2020.12
System Design
VLT® Soft Starter MCD 600
Operating Guide

Table of Contents

Other manuals for Danfoss VLT MCD 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 600 and is the answer not in the manual?

Danfoss VLT MCD 600 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 600
CategoryController
LanguageEnglish

Related product manuals