Application
Start mode
Start
ramp
time [s]
Initial
current
[%]
Cur-
rent
limit
[%]
Adaptive
start profile
Stop mode
Stop
time [s]
Adaptive
stop profile
Compressor re-
ciprocating
Constant cur-
rent
2
200
450
n/a
Coast to stop
n/a
n/a
Conveyor
Constant cur-
rent
5
200
450
n/a
Coast to stop
n/a
n/a
Bow thruster
Constant cur-
rent
5
100
400
n/a
Coast to stop
n/a
n/a
Bandsaw
Constant cur-
rent
2
200
450
n/a
Coast to stop
n/a
n/a
N O T I C E
The adaptive start and stop profile settings only apply when using adaptive control. The settings are ignored for all other start
and stop modes.