Table 118: 6-3 - Current Imbalance
Selects the soft starter's response to each protection.
All protection events are written to the event log.
The soft starter stops the motor as selected in parameter 2-9 Stop Mode or parameter 3-11 Stop Mode, then
enters trip state. The trip must be reset before the soft starter can restart.
The soft starter stops the motor as selected in parameter 2-9 Stop Mode or parameter 3-11 Stop Mode, then
enters trip state. The trip resets after the auto-reset delay.
The soft starter removes power and the motor coasts to stop. The trip must be reset before the soft starter
can restart.
The soft starter removes power and the motor coasts to stop. The trip resets after the auto-reset delay.
The protection is written to the event log and the display shows a warning message, but the soft starter
continues to operate.
The protection is written to the event log but the soft starter continues to operate.
The soft starter removes power and the motor coasts to stop. The shunt trip relay (13, 14) activates and the
circuit breaker disconnects mains voltage from the soft starter. The circuit breaker must be manually reset
before operation can resume. This option is only effective if parameter 20-8 Shunt Trip Mode is set to Enable.
Table 119: 6-4 - Undercurrent
Selects the soft starter's response to the protection event.
Table 120: 6-5 - Overcurrent
Selects the soft starter's response to the protection event.