9.3 Second level menu - BC (Basic settings)
BC - Basic settings
Display Description Selections available
AC - Enabling of automatic closure
OF - Disabled
ON - Enabled
1-2 - Dependent on input 30-2
hR - Push-to-operate “dead man” closure (independently of
setting of parameter R9)
hr - Push-to-operate “dead man” closure, obliged until
complete closure (independently of setting of parameter R9)
NOTE: in hr mode if the closure command is removed
before reaching the closed position limit switch, the
door/gate re-opens automatically.
SS - Selection of automation status at start-up
OP - Open
CL - Closed
Indicates how the control panel considers the automation at the time
of switch-on, or after a POWER RESET command.
SO - Enabling of reversal safety contact functioning during opening
ON - Enabled
OF - Disabled
When enabled (ON) with the automation idle, if the contact 1-8 is open, all oper-
ations are prevented.
When disabled (OF) with the automation idle, if the contact 1-8 is open, opening
operations are permitted.
NI - Enabling of NIO electronic anti-freeze system
ON - Enabled
OF - Disabled
When enabled (ON), it maintains the efficiency of the motor even at low ambient
temperatures.
NOTE: for correct operation, the control panel must be exposed to the same
ambient temperature as the motors.
The intervention temperature for the NIO system can be set by selecting
→ .
WARNING: When the NIO system is in operation, the 230 V~ (LP~) flashing light
output will remain activated. The NIO function cannot be used when motors
with limit switches series connected to the phases (FA/FC= MT) are used.