Electrical Installation
11
Electrical Installation
Field cables specification. -The cables are required to supply between 18 and 32V DC at peak current (all lamps and heaters on). Figure
3 below shows typical values of peak current consumption for Transmitter and Receiver individually. The field cable runs must comply with
local regulations. Please refer to the Tables over for maximum recommended power cable lengths.
Figure 3: Peak current consumption
Tx current consumption
Rx current consumption
Voltage DC
004223892.eps
600
550
500
450
400
350
300
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
585
336
346
367
378
388
399
420
430
441
451
472
483
462
409
357
571
558
546
535
525
517
509
502
496
492
488
485
484
483