EasyManuals Logo
Home>Dräger>Security Sensors>Polytron Pulsar 2

Dräger Polytron Pulsar 2 User Manual

Dräger Polytron Pulsar 2
57 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
AMS operator screens and help texts
50
Figure 23 Configuration Properties of AMS Tag (Last zeroing)
1
Proper selection of Channel avoids interference with other instru-
ments nearby. Receiver and Transmitter must have the same
Channel whereas neighbouring Dräger Polytron Pulsar 2s should
be set to a different Channel.
2 Duration Dräger Polytron Pulsar 2 has operated. This total is
maintained by a non-volatile memory within the
Dräger Polytron Pulsar 2 Receiver. A period up to 2 hours may
be lost when the Receiver is re-powered.
3 Signal strength depends on the operating distance and the
presence of fog. Misalignment of the Transmitter and the
Receiver and dirt on their lenses can also affect this value.
4 Signal strength recorded at time of last zeroing. This value is
subsequently compared with the Best Recent Strength to
determine whether the lenses of the Transmitter and Receiver
need cleaning.
5 The value of 'Operation Hours' recorded the most recent time
the Dräger Polytron Pulsar 2 was zeroed.
6 The Dräger Polytron Pulsar 2 was set to this channel when last
zeroed.
7 The Dräger Polytron Pulsar 2 was last zeroed without the data
link connected between Receiver and Transmitter.
8 The Dräger Polytron Pulsar 2 was last zeroed with other equip-
ment than an ES (2/4Hz Enhanced Speed)
9 Device has never been zeroed. In this case further data corre-
sponding with the last zeroing are of no meaning.
6
5
4
7
8
9
3
2
1
02923892.eps

Table of Contents

Other manuals for Dräger Polytron Pulsar 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dräger Polytron Pulsar 2 and is the answer not in the manual?

Dräger Polytron Pulsar 2 Specifications

General IconGeneral
BrandDräger
ModelPolytron Pulsar 2
CategorySecurity Sensors
LanguageEnglish

Related product manuals