PACSystems™ RX3i and RSTi-EP CPU Reference Manual Section 6
GFK-2222AK October 2019
Serial I/O, SNP & RTU Protocols 142
6.2.3 Status Word for Serial I/O COMMREQs
A value of 1 is returned in the COMMREQ status word upon successful completion of the
COMMREQ. Any other value returned is an error code where the low byte is a major error
code and the high byte is a minor error code.
Major Error Code
Description
01 (01h)
Successful Completion
(this is the expected completion value in the COMMREQ status
word).
12 (0Ch)
Local error Error processing a local command.
The minor error code identifies the specific error.
02 (02h)
COMMREQ command is not supported.
06 (06h)
Invalid CPU memory type specified.
07 (07h)
Invalid CPU memory offset specified.
08 (08h)
Unable to access CPU memory.
12 (0Ch)
COMMREQ data block length too small.
14 (0Eh)
COMMREQ data is invalid.
15 (0Fh)
Could not allocate system resources to complete
COMMREQ.

Table of Contents

Other manuals for Emerson PNC001-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson PNC001-A Series and is the answer not in the manual?

Emerson PNC001-A Series Specifications

General IconGeneral
BrandEmerson
ModelPNC001-A Series
CategoryController
LanguageEnglish

Related product manuals