PACSystems™ RX3i and RSTi-EP CPU Reference Manual Section 2
GFK-2222AK October 2019
CPU Features & Specifications 26
2.2 RX3i CPU Features and Specifications
CPU310
CPU315
CPU320/
CRU320
21
CPE302
22
/
CPE305
CPE310
CPE330
CPE400/
CPL410
Lifecycle Phase
Discontinued -
use CPE310
Discontinued -
use CPE310
or CPE330
Discontinued -
use CPE330
Active
Active
Active
Active
Operating System
VxWorks
VxWorks
VxWorks
VxWorks
VxWorks
VxWorks
VxWorks
#RX3i Slots Occupied
2
2
2
1
2
2
N/A
Backplane
<----------------------Supports High-Speed PCI IC695* and Serial IC694* Modules -------------------------->
Field Agent
(CPE400) /
Linux (CPL410)
Temperature Range
RX3i
0°C to 60°C
0°C to 60°C
0°C to 60°C
0°C to 60°C
23
0°C to 60°C
15
0°C to 60°C
-40°C to 70°C
24
Power Requirements
RX3i +3.3Vdc
1.25 A
1.0 A
1.0 A
1.0 A
1.0 A
0 A
N/A
RX3i +5 Vdc
1.0 A
1.2 A
1.2 A
1.0 A
(up to 1.5 A if
USB draws 0.5A)
1.0 A
(up to 1.5 A if
USB draws 0.5A)
0 A
N/A
RX3i +24Vdc Relay with Energy Pack
0.5 A at start-up;
0.1 A otherwise
0.5 A at start-up;
0.1 A otherwise
0.750 A
N/A
RX3i +24Vdc Relay w/o Energy Pack
0.625 A
N/A
Input Power (Max)
20 W
Input Voltage (Min)
18 Vdc
Input Voltage (Max)
30 Vdc
Memory Backup Mechanism
25
Battery
see GFK-2741
Battery
see GFK-2741
Battery
see GFK-2741
Energy Pack:
IC695ACC400
Energy Pack:
IC695ACC400
Energy Pack:
IC695ACC402
Energy Pack:
IC695ACC403
Display
21
For CRU-type CPUs, see Redundancy section at bottom of this table.
22
Where different, CPE302 value is shown in parentheses (). Also note that first Firmware Version of CPE302 was FW 9.40.
23
LT versions of the hardware are rated from -40°C to 60°C.
24
The maximum operating temperature varies according to installation altitude: 70
C at 0m to 2000m, 65
C at 2000m to 3000m, and 60
C at 3000m to 4000m.
25
See Battery Compatibility and Memory Retention (Time in Days at 20°C) in GFK-2741

Table of Contents

Other manuals for Emerson PNC001-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson PNC001-A Series and is the answer not in the manual?

Emerson PNC001-A Series Specifications

General IconGeneral
BrandEmerson
ModelPNC001-A Series
CategoryController
LanguageEnglish

Related product manuals