12 • Technical Specifications
Phase Loss, Under/over
Frequency:
Trips when one or two phases are missing, or frequency is < 40Hz or > 65Hz.
Optional auto reset.
Phase Sequence: Trips when phase sequence is wrong
Long Slow Speed Time: Trips if operating at slow speed TRQ for more than 1-30 sec (1-250 sec
9
)
Wrong Connection: Prevents starting, trips if motor is not connected / incorrectly connected to the
ASTAT-XT (not active in D.Set: Generator Parameters)
Shorted SCR: Trips if one or more SCRs have been shorted
(not active in D.Set: Generator Parameters)
Heat Sink Over
Temperature:
Trips when heat-sink temperature rises above 85°C
External Fault: Trips when an external contact closes for 2 sec.
Motor Thermistor: Trip level setting 1-10K, trips when resistance decreases below the level set
Control:
Displays: LCD in 4 – Field selectable languages and 8 LEDs
Keypad: 6 keys for easy setting
Aux Contact – Immediate: 1 C/O, 8A, 250VAC, 2000VA
Aux Contact – End Of
Ramp:
1 C/O, 8A, 250VAC, 2000VA
Fault Contact: 1 C/O, 8A, 250VAC, 2000VA
Communication: RS 485 with Modbus protocol for full control and supervision
Communication (optional): Profibus DPV1 for full control and supervision
Communication (optional): DeviceNet
tm
for full control and supervision
Temperatures Operating: -10° to 50°C
Storage: -20° to 70°C
Standards:
Dielectric Test: 2500VAC
Degree of Protection: IP 20 for QTx0008 - QTx0072 ; IP 00 for QTx0085 – QTx1400
Pollution Degree: 3
EMC Emissions: EN 61000-6-4 CISPR 11 Class A
Immunity: EN 61000-6-2 ESD 8KV air, IEC 801-2;
Electric RF field 10 V/m, 20-1000Mhz, IEC 801-3
Fast transients 2KV, IEC 801-4
Safety: EN IEC 600947-4-2 and EN IEC 60947-1 Related to safety requirements.
UL508C
Rated Operational Current AC:53a:4-30: 50-4
Normal Service Conditions:
Altitude: Up to 1000m.
Humidity: 95% at 50°C or 98% at 45˚C
Fan and Control Consumption Ratings:
QTx0008 to QTx0031: No fan Total approximate consumption: 150VA
QTx0044 to QTx0072: Fan 35 VA Total approximate consumption 185VA
QTx0085 to QTx0170 :Fan 60 VA Total approximate consumption 210VA
QTx0210 to QTx0390 : Fans 105 VA (35VA x 3) Total approximate consumption 255VA
QTx0460 to QTx1400A : Fans 150 VA (50VA x 3) Total approximate consumption 300VA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE ASTAT XT QT 0008U Series and is the answer not in the manual?

GE ASTAT XT QT 0008U Series Specifications

General IconGeneral
BrandGE
ModelASTAT XT QT 0008U Series
CategoryController
LanguageEnglish

Related product manuals