73 • Application diagrams
Soft Starter
Bussman Fuses DIN 43620
Rated Current Rated
Current
Breaking
Capacity
A A
2
Sec A P/No. Size Un Type KA
8 400 40 170M3808D 1 690 H.S.D.I. 200
17 5000 63 170M3810D 1 690 H.S.D.I. 200
31 10000 125 170M3813D 1 690 H.S.D.I. 200
44 12000 160 170M3814D 1 690 H.S.D.I. 200
58 15000 160 170M3814D 1 690 H.S.D.I. 200
72 18000 200 170M3815D 1 690 H.S.D.I. 200
85 50000 250 170M3816D 1 690 H.S.D.I. 200
105 60000 315 170M3817D 1 690 H.S.D.I. 200
145 10000 315 170M3817D 1 690 H.S.D.I. 200
170 140000 400 170M3819D 1 690 H.S.D.I. 200
210 200000 500 170M4864D 1 690 H.S.D.I. 200
310 600000 500 170M4864D 1 690 H.S.D.I. 200
390 700000 800 170M5814D 2 690 H.S.D.I. 200
460 800000 900 170M6813D 3 690 H.S.D.I. 200
580 1200000 1000 170M6814D 3 690 H.S.D.I. 200
650 2000000 2x800 2x170M5814D 2x2 690 H.S.D.I. 200
820 2000000 2x800 2x170M5814D 2x2 690 H.S.D.I. 200
950 4500000 2x1000 2x170M5816D 2x2 690 H.S.D.I. 200
1100 4500000 2x1100 2x170M6892D 2x2 690 H.S.D.I. 200
1400 6500000 2x1400 2x170M8555D 2x3 690 H.S.D.I. 200
8.19 Transient Protection
Line transien
t voltages can cause a malfunction of the ASTAT-XT and damage to the thyristors. All ASTAT-XTs
incorporate Metal Oxide Varistors (MOV) to protect from normal line voltage spikes.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE ASTAT XT QT 0008U Series and is the answer not in the manual?

GE ASTAT XT QT 0008U Series Specifications

General IconGeneral
BrandGE
ModelASTAT XT QT 0008U Series
CategoryController
LanguageEnglish

Related product manuals