98 Appendix A - MODBUS RTU Protocol
Example 9:
To read all discrete inputs of ASTAT-XT # 12, the host computer sends the following Query frame:
byte 1: Serial Link No. ($0C) (12)
byte 2: Function ($02)
byte 3: Starting Address High ($00)
byte 4: Starting Address Low ($00)
byte 5: No. of Points High ($00)
byte 6: No. of points Low $08)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)
The ASTAT-XT response when only Stop and Soft Stop terminals (Inputs 1&2) are connected:
byte 1: Serial Link No. ($0C) (12)
byte 2: Function ($02)
byte 3: Byte Count ($01)
byte 4: Data (Inputs 7..0) ($03)
byte 5: CRC_Low ($XX)
byte 6: CRC_High ($XX)
A.12. Diagnostics
Modbus Function 08 as implemented in the ASTAT-XT supports only Subfunction $0000. It provides for the
"loopback" (Return Query Data) feature, and for checking the Communication Serial Link between the master and
the ASTAT-XT.
To request ASTAT-XT # 1 to return Query data, the master should send following Query frame:
byte 1: Serial Link No. ($01)
byte 2: Function ($08)
byte 3: Subfunction High ($00)
byte 4: Subfunction Low ($00)
byte 5: Data High ($37)
byte 6: Data Low ($A5)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)
The Normal (if no exception) response is the echo of the Query:
byte 1: Serial Link No. ($01)
byte 2: Function ($08)
byte 3: Subfunction High ($00)
byte 4: Subfunction Low ($00)
byte 5: Force Data High ($37)
byte 6: Force Data Low ($A5)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE ASTAT XT QT 0008U Series and is the answer not in the manual?

GE ASTAT XT QT 0008U Series Specifications

General IconGeneral
BrandGE
ModelASTAT XT QT 0008U Series
CategoryController
LanguageEnglish

Related product manuals