97 • Appendix A - MODBUS RTU Protocol
byte 3: Coil Address High ($00)
byte 4: Coils address Low ($02)
byte 5: No. of Coils High ($00)
byte 6: No. of coils Low ($03)
byte 7: Byte Count ($01)
byte 8: Force Data ($07)
byte 9: CRC_Low ($XX)
byte 10: CRC_High ($XX)
The Normal (if no exception) response is the echo of the Query:
byte 1: Serial Link No. ($20)
byte 2: Function ($0F)
byte 3: Coil Address High ($00)
byte 4: Coils address Low ($02)
byte 5: No. of Coils High ($00)
byte 6: No. of coils Low ($03)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)
A.11. Discrete Hardwired Inputs (1x References)
The ASTAT-XT incorporates 16 Discrete Inputs, (bit parameters), from which only 6 are operative. The other 10 are
reserved and were incorporated to enable use of word (16 bits) type parameters. Input # is "1 based". The actual
address is 1 lower than input #. For example input #1 is addressed as 0 (10000). The inputs have the following 1x
references:
Input # Address ASTAT-XT use Comment
1 0 Stop Open Input (Input reads" 0") to Stop. (Terminal # 4)
Close Input (Input reads "1") to enable Start / Run.
2 1 Soft Stop Open Input (Input reads"0") to Soft Stop. (Terminal # 5)
Close Input (Input reads"1") to enable Start / Run.
3 2 Start Close Input (Input reads "1") to Start. (Terminal # 6)
4 3 Energy Save * (Terminal # 7)
Slow Speed *
Reset * Close Input (Input reads "1") to turn On.
Open Input (Input reads "0") to turn Off.
5 4 Dual Adjust * (Terminal # 8)
S. Spd Rvrs *
Reset * Close Input (Input reads "1") to turn On.
Open Input (Input reads "0") to turn Off.
6..7 5 Reserved
8 7 External Fault Open Input = no fault (Input reads" 0") (Terminal #19)
indicates No Fault Condition.
9..16 8..15 Reserved
* Programmable inputs.