95 Appendix A - MODBUS RTU Protocol
Notes:
1. The Read function of the control register is not possible. To read the ASTAT-XT status, read the Logic_Status
(Actual parameter # 1).
2. Bytes 2..8 of the control frame must be exactly as in the following example. Otherwise an error message is
returned.
3. Hardwired Stop and Soft Stop inputs override the communication. To enable motor starting through
communication, terminals 4 and 5 (Stop & Soft stop) must be connected to the control voltage.
Example 5 - Control Register Write:
To start ASTAT-XT # 11, the host computer sends the following Query frame:
byte 1: Serial Link No. ($0B)
byte 2: Function ($10) Bytes 2..8 must be as in this example!!!
byte 3: Starting Address High ($02)
byte 4: Starting Address Low ($F0)
byte 5: No. of Registers High ($00)
byte 6: No. of Registers Low ($01)
byte 7: Byte Count ($02)
byte 8: Data High ($5A)
byte 9: Data Low ($04) Bit 2 is set, to start.
byte 10: CRC_Low ($XX)
byte 11: CRC_High ($XX)
The ASTAT-XT Normal response:
byte 1: Serial Link No. ($0B)
byte 2: Function ($10)
byte 3: Starting Address High ($02)
byte 4: Starting Address Low ($F0)
byte 5: No. of Registers High ($00)
byte 6: No. of Registers Low ($01)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)
A.10. Discrete Commands (Coils, 0x References)
The ASTAT-XT incorporates 16 "Coils", (bit parameters), of which only 5 are operative. The other 10 are reserved and
were incorporated to enable the user to use word (16 bits) type parameters. Coil # is 1"1 based". The actual address
is 1 lower than coil #. For example coil #1 is addressed as 0 (00000). The coils have the following 0x references:
Coil # Coil Address Use in ASTAT-XT Comment
1 0 Stop Write "1" (ON) to stop.
2 1 Soft Stop Write "1" (ON) to Soft Stop
3 2 Start Write "1" (ON) to start
4 3 Energy Save Write "1" (ON) to turn On. Write "0" (OFF) to turn Off.
5 4 Dual Adjust Write "1" (ON) to turn On. Write "0" (OFF) to turn Off.
6 5 Slow Speed Write "1" for Slow Speed. Write "0" for Normal Start.
7 6 Slow Spd Reverse Write "1: for Reverse Direction. Write "0" for Forward Direction
8 7 Reset Write "1" (ON) to Reset.
9..16 8..15 Reserved
Example 6 - Read Coils:
To read coils 1..8 status of ASTAT-XT # 10, the host computer sends the following Query frame:
byte 1: Serial Link No. ($0A)
byte 2: Function ($01)
byte 3: Starting Address High ($00)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE ASTAT XT QT 0008U Series and is the answer not in the manual?

GE ASTAT XT QT 0008U Series Specifications

General IconGeneral
BrandGE
ModelASTAT XT QT 0008U Series
CategoryController
LanguageEnglish

Related product manuals