40 • Control Keypad
4.7.8 I/O Settings Parameters
41
– Page 7
Function &
Default
Range Unit Description
PROG. Input # 7
Reset
Reset;
Slow Speed;
Energy Saving
Sets the terminal 7 function
Refer to section
4.7.8.1 on page 41.
PROG. Input # 8
Dual Settings
Dual Settings;
Slow SPD
Reverse;
Reset;
Sets the terminal 8 function
Refer to section
4.7.8.1 on page 41.
PROG. Fault Relay
At Fault Close
At Fault Close,
At Fault Open
Sets the Fault Relay mode of operation.
When configured to At Fault Close the internal
relay is energized upon fault.
When configured to At Fault Open the relay is de
-
energized upon fault. In this mode, while normal
operation, the fault relay is energized.
Relay will also de
-energize upon control power outage.
Relay ON Delay
0 SEC.
0 – 3600 sec. Sets ASTAT-XT’s Immediate Relay (RUN relay)
ON delay time.
Relay OFF Delay
0 SEC.
0 – 3600 sec. Sets ASTAT-XT’s Immediate Relay (RUN relay) OFF delay
time.
Analog Output
I, 0...200% OF Im
I, 0...200% OF Im
Sets Analog Output mode of operation.
The dip switch settings on the analog card define full
scale as either 20mA or 10V. Refer to section
5.7 on
page 51 for more details.
The full s
cale of the analog card is related to 200% of
Motor Current
(2x <rated motor current>).
Store Settings
I/O Settings
Same as Store Settings Main Settings on
page 28.
41
Displays in MINIMIZED MODE and MAXIMIZED MODE.