16 • Technical Specifications
Terminal Function Description
Terminal SG No connection Standard RS485, half duplex with Modbus protocol, baud
rate 1200, 2400, 4800, 9600 BPS.
Terminal D- RS-485 communication (-) Twisted shielded pair should be used.
Connect shield to ground on the PLC/Computer side.
Terminal D+ RS-485 communication (+) Terminals 4 & 5 must be wired to Control Supply for
operation in communication mode (refer to section
8.16
page 70 for wiring diagram).
Up 32 units can be connected for Modbus RS485
communication. For reliable communication, units should
be installed in the vicinity of 200m maximum, from the first
to the last unit.
Refer to section 4.7.9 page 42 for programming.
Refer to Appendix A of this manual for Modbus protocol
manual.
Terminal 28 Thermistor input (T1) Thermistor input is programmable as a PTC or NTC type
thermistor. The trip value is adjustable between 1-10Kohm,
preset delay of 2 Sec.
Terminal 29 Thermistor input (T2)
Connect thermistor and/or Analog output shield to ground
terminal.
Terminal 30 Ground Analog output (0-10VDC or 0-20mA or 4-20mA)
Terminal 31 Analog output (-) Reflects motor current and is related to 2xIm. i.e., Full scale
(10VDC or 20mA) is related to 2xIm.
Terminal 32 Analog output (+) Note:
Refer to section
5.7 page 51 for analog output PCB dip switch
setting.
Refer to section 4.7.8 page 40 for Analog Output
programming.
Refer to section 4.7.7 page 38 for Thermistor Type and
Thermistor Trip programming.
D-9 connector Profibus communication
(optional)
Profibus DPV0 and DPV1, up to 12 MBPS.
D type 9 pin connector is applied.
Control, monitoring and setting parameters can be achieved
via the Profibus connection.
Setting is possible only when DPV1 is implemented.
Refer to section 4.7.10 page 42 for programming.
Refer to Appendix B of this manual for Profibus protocol
manual.
Terminal V- 0 Volt external power supply
Terminal CL Negative data line
Terminal Dr Cable shield
Terminal CH Positive data line
Terminal V+
DeviceNet communication
(optional)
+24V external power supply

Table of Contents